Nitrate and nitrite

Far West Water & Sewer Inc

Nitrate and nitrite enter water from fertilizer runoff, septic tanks and urban runoff. These contaminants can cause oxygen deprivation for infants and increase the risk of cancer. Nitrite is significantly more toxic than nitrate. Click here to read more about nitrate.

 

25

Samples

0

Samples exceeding legal limit (MCL)

20

Samples exceeding
health guidelines

Testing results - average by year

 
YearAverage resultSamples takenDetectionsRange of results
20142.14 ppm53ND - 7.40 ppm
20151.40 ppm54ND - 3.90 ppm
20161.06 ppm550.210 ppm - 2.30 ppm
20171.84 ppm53ND - 8.10 ppm
2018N/A00N/A
20190.558 ppm550.260 ppm - 1.20 ppm

ppm = parts per million

State and national drinking water standards and health guidelines

EWG Health Guideline 0.14 ppm

The health guideline of 0.14 parts per million, or ppm, for nitrate and nitrite is based on the equivalent health guideline for nitrate, as defined in a peer-reviewed scientific study by EWG. This guideline represents a one-in-one-million annual cancer risk level.

EPA Maximum Contaminant
Level (MCL) 10 ppm

ppm = parts per million

All test results

Date Lab ID Result
2014-02-03550-18903-1ND
2014-02-03550-18901-13.00 ppm
2014-02-03550-18898-1ND
2014-02-03550-18888-10.300 ppm
2014-03-05550-20741-17.40 ppm
2015-01-07550-38044-1I3.90 ppm
2015-01-07550-38043-1I2.20 ppm
2015-01-07550-38042-10.350 ppm
2015-01-14550-38498-1IND
2015-05-18550-45029-10.570 ppm
2016-01-18550-57438-22.30 ppm
2016-01-18550-57423-20.210 ppm
2016-01-25550-57775-10.630 ppm
2016-01-25550-57774-10.280 ppm
2016-02-22550-59253-11.90 ppm
2017-01-09550-75570-1I8.10 ppm
2017-01-09550-75557-10.230 ppm
2017-01-23550-76324-1ND
2017-01-23550-76323-10.860 ppm
2017-01-23550-76322-1ND
2019-02-26550-118559-10.290 ppm
2019-02-26550-118560-10.300 ppm
2019-02-26550-118559-40.260 ppm
2019-02-26550-118559-31.20 ppm
2019-02-26550-118559-20.740 ppm